Technical Summary
Rating Range
120 to 600V, single phase and three phase @ 50/60 Hz
Transfer Type
Switch application dependent
Switch Type
Switch application dependent
ATC Controller Specifications
Input Control Voltage
Voltage Measurements of Utility
Source 1 VAB Source 2 VAB
Source 1 VAC Source 2 VBC
Source 1 VCA Source 2 VCA
Voltage Measurement Range
0 to 790 VAC rms (50/60 Hz)
Voltage Measurement Accuracy
+/-2% of nominal input voltage
Frequency Measurements Of
Frequency Measurement Range
Frequency Measurement Accuracy
Undervoltage Dropout
50% to 90% of nominal voltage
Undervoltage Pickup
(Dropout +2%) to 99% of the nominal system voltage
Underfrequency Dropout Range
90 to 97% of the nominal system frequency
Underfrequency Pickup Range
(Dropout +1 Hz) to 99% of the nominal system frequency
Overfrequency Dropout Range
103 to 110% of the nominal system frequency
Overfrequency Pickup Range
101% to (dropout - 1 Hz) of the nominal system frequency
Operating Temperature Range
-20 to 70 degree C (-4 to +158 degree F)
Storage Temperature Range
-30 to 85 degree C (-22 to +185 degree F)
Operating Humidity
0 to 95% relative humidity (noncondensing)
Operating Environment
Resistant to ammonia, methane, nitrogen,hydrogen and hydrocarbons
Generator Start Relay
5A, 1/6 hp @ 250 Vac Vac 5A @ 30 Vdc with a 150W maximum load
K1, K2 Relays
10A, 1-3 hp @ 250 Vac
10A@30 Vdc
Applicable Testing
UL-recognized component
Meets intent of UL 991 & UL 1008
Meets IEC 1000-4-2, 1000-4-3, 1000-4-4
Applicable Testing Continued
1000-4-5, 1000-4-6, 1000-4-11
CISPR 11, Class A
FCC Part 15, Class A
CSS 22.2-178
Enclosure Compatibility
NEMA 1, NEMA 3R and NEMA 12
UV-resistant ATC-300+ faceplate